GE Recalls Air Conditioning and Heating Units Due to Risk of Fire
3rd Nov 2015
Recall Summary
Name of product:
GE Zoneline® Air Conditioners and Heating Units
Hazard:
Moisture from outdoor air can accumulate near the unit’s heater when the unit is operated with the vent door continuously open. This, along with two shorted electrical components, can create an electrical ground path and arcing, posing a risk of fire.
Recall Details
Units
About 33,500
Description
This recall involves GE Zoneline Packaged Terminal Air Conditioners (PTAC) and heating units with listed serial numbers. These units are most often used in hotels, apartment buildings and commercial spaces. The GE logo is affixed to the control panel door. Units with the following models and serial numbers are included in this recall:
Brand | Model Prefix | Serial Number (Begins with) |
GE | AZ40E09E AZ41E07E AZ41E09E AZ41E12E AZ41E15E AZ61H07E AZ61H09E AZ61H12E AZ61H15E | AT, AV, AZ, DT, DV, DZ, FT, FV, FZ, GS, GT, GV, GZ, HT, HV, HZ, LT, LV, LZ, MT, MV, MZ, RT, RV, RZ, ST, SV, SZ, TT, TV, TZ, VS, VT, VV, VZ, ZS, ZT, ZV, ZZ |
The model and serial numbers are printed on the rating plate that can be seen after removing the front panel.
Incidents/Injuries
GE has received three reports involving smoke and/or fire associated with the unit’s heater resulting in about $30,000 of property damage. No injuries have been reported.
Remedy
Consumers should contact GE to schedule a free repair. Do not operate the PTAC unit with the external vent open while awaiting a free repair. Property maintenance personnel should remove the unit’s front panel and locate the vent door control lever at the left side of the Zoneline unit to ensure the lever is in the closed position.
Sold at
GE authorized representatives and HVAC distributors nationwide from January 2010 through December 2013 for between $1,000 and $1,200.
Importer(s)
GE Appliances, of Louisville, KY
Manufactured in
China